The publisher’s own README, as collected from the registry.
A BACnet/IP device simulator with a live web UI. Simulate lighting controllers, air conditioners, AHUs, power meters, sensors, PV inverters — or any device you describe in YAML — and watch their values change in the browser while a real BACnet client (Yabe, Niagara, your own EMS…) reads and commands them.
Built on bacpypes3 (asyncio BACnet stack, supports BACnet/IP, IPv6 and BACnet/SC) and FastAPI. No front-end build step.
SME BACnetSim is free and MIT-licensed, developed by smart-edge (智届科技) — custom development is available, see Commercial support & custom development.
python -m venv .venv
.venv\Scripts\pip install -r requirements.txt
.venv\Scripts\python -m sme_bacnet_sim --config configs/demo-building.yaml
Open http://127.0.0.1:8080/ . Options:
| Option | Meaning |
|---|---|
-c, --config FILE |
YAML/JSON config (defaults to configs/demo-building.yaml) |
--ip 192.168.1.10/24 |
NIC address for BACnet/IP (default: auto-detect, /24) |
--bacnet-port 47808 |
BACnet/IP UDP port |
--foreign-bbmd 192.168.2.1[:47808] |
Register as a foreign device with this BBMD (overrides config) |
--foreign-ttl 300 |
Foreign device Time-to-Live in seconds (overrides config) |
--host 0.0.0.0 --http-port 8080 |
Web UI bind address (default localhost only) |
--browser |
Open the web UI in a browser on start (not opened by default; --no-browser is the default) |
The client sees the router (device 4194000) at <ip>:47808 and the simulated devices at addresses such as
100:1, 100:2 (network 100, MAC 1, 2…) routed through it. In Yabe: Add device → BACnet/IP over UDP,
then Who-Is.
Same PC caveat: on Windows, a client on the same machine may not receive broadcast replies (Who-Is/I-Am) — unicast works. Run the client on another machine, bind the simulator to a different NIC than the client, or set
network.mode: bbmdand register the client as a foreign device.
Client on another UDP port: Who-Is / I-Am broadcasts go to the simulator's port (47808 by default). A client bound to another port (e.g. 47809) does not receive the I-Am broadcasts and finds no devices. Either use the same port on both sides, or set
network.mode: bbmdand register the client as a foreign device with the simulator (<simulator ip>:47808); the I-Am replies are then forwarded to the client.
Edit → BACnet network… (or a click on the BACnet/IP address in the status bar) changes the network adapter
(listed by name and address/prefix, or Auto-detect), the UDP port, the IP-side and virtual network numbers, the
router device ID and the mode (normal / BBMD / foreign device with BBMD address and TTL). Apply checks the settings
(an address of this computer, a free UDP port, different network numbers, unique device IDs), rebinds BACnet/IP
without restarting and writes the network: section back to the config file (other sections and unsaved edits are
left as they are; comments inside network: are lost). Command-line options such as --ip / --bacnet-port still
win at the next start. Clients have to discover the devices again after a change.
Not supported: switching off Read-Property-Multiple or segmentation support (always on).
docker run --rm --network host -e TZ=Asia/Tokyo ghcr.io/smartedge-tech-dev/sme-bacnet-sim:<ver>
--network host (Linux) is needed for Who-Is / I-Am broadcasts. Without TZ the container clock is UTC, and
schedules and the clock in the UI follow it (the image includes tzdata).
To reach clients on another subnet, the router port can register as a foreign device with an existing BBMD:
network.foreign_device: {bbmd: "<ipv4>[:port]", ttl: <seconds>} or --foreign-bbmd / --foreign-ttl
(the command line wins; TTL defaults to 300 s, port to 47808). The registration uses bacpypes3's foreign
link layer: it is renewed every TTL, retried while unanswered, and cancelled (TTL 0) on stop or reload. Results
(registered / NAK / no answer within 10 s / expired) are written to the event log and shown in the status bar as
FD → <bbmd> (…); the snapshot API reports them in network.foreign_device.
Not supported: combining foreign_device with mode: bbmd, BBMD host names (IPv4 literals only), and reading
or editing the BBMD's tables (Read-Broadcast-Distribution-Table, Read-Foreign-Device-Table and similar).
network:
ip: auto # or "192.168.1.10/24"
port: 47808
network_number: 1 # IP-side network number
virtual_network: 100 # network number of the simulated devices
mode: normal # or bbmd
# foreign_device: {bbmd: "192.168.2.1:47808", ttl: 300} # register with an external BBMD
router: {device_id: 4194000, name: SME-BACnetSim-Router}
simulation:
tick_seconds: 1.0
time_scale: 1.0 # 60 = 1 simulated minute per second
history_size: 600 # trend samples kept per point
devices:
- device_id: 1002
name: AC-1F-East
template: split_ac # optional
params: {rated_kw: 2.8} # template parameters
objects: # add objects, or override template objects by name
- {name: SetPoint, type: av, value: 24.0, commandable: true}
| Key | Notes |
|---|---|
type |
ai ao av bi bo bv msi mso msv acc pc loop file prog tl sch cal nc ee (or full names such as analog-input, trend-log, schedule, calendar, notification-class, event-enrollment) |
instance |
optional; auto-numbered per type |
name, description |
name is also the variable name in expressions |
units |
BACnet engineering units, e.g. degrees-celsius, kilowatts, percent |
value |
initial value (binary: 0/1, multi-state: 1-based index) |
states |
multi-state texts |
active_text, inactive_text |
binary texts (quote "ON"/"OFF" — YAML reads them as booleans) |
commandable |
for av/bv/msv; outputs are always commandable |
min, max, cov_increment |
analog limits and COV increment |
behavior |
how the value is simulated (below) |
log_object, log_property, log_interval, logging_type, client_cov_increment, buffer_size, enabled |
trend logs only (below) |
weekly, exceptions, default, targets, priority_for_writing, effective_period |
schedules only (below) |
dates |
calendars only (below) |
scale, prescale |
accumulators only (below) |
scale_factor, input_object |
pulse converters only (below) |
controlled_object, manipulated_object, setpoint, setpoint_object, proportional_constant, integral_constant, derivative_constant, bias, action, update_interval |
loops only (below) |
file_type, access, content, path, read_only, program_state, instance_of, program_location |
files and programs only (below) |
monitored_object, event_type, event_parameters, notification_class, event_enable, notify_type, time_delay, time_delay_normal |
event enrollments only (below) |
- {type: acc, name: EnergyPulses, units: kilowatt-hours, scale: 0.01, max: 99999999,
behavior: {type: pulse, rate: "ActivePower * 100 / 3600"}}
- {type: pc, name: EnergyFromPulses, input_object: EnergyPulses, scale_factor: 0.01, units: kilowatt-hours}
- type: loop
name: SupplyTempLoop
controlled_object: SupplyTemp # controlled-variable-reference (present-value)
manipulated_object: CoolValve # manipulated-variable-reference (present-value)
setpoint_object: SupplyTempSP # or a fixed setpoint: 16
proportional_constant: 8
integral_constant: 0.2
min: 0 # minimum-output
max: 100 # maximum-output
units: percent # output-units
priority_for_writing: 10 Find threats in your stack.
OX Radar can check high-priority threats, like critical package CVEs, against your context.
Each incident is marked Detected or Not Detected with a remediation plan and proof all tracked in the Response Center.
The probe returned only these fields for this server — auth requirement, protocol and tool list weren’t observed, so they’re not shown (never guessed).
The publisher’s own links, as the registry reports them. These are not sources for the assessment on this page.